A three-phase system uses three AC phase quantities separated by 120 electrical degrees when balanced. Loads and windings are commonly connected in star (wye) or delta. The connection determines how line quantities measured at the supply terminals relate to phase quantities measured at each branch.
Star connection
In star, one end of each branch joins a common point. A neutral conductor can connect to this point, but some star loads use only the three line conductors. In a balanced system, V_L=\sqrt3\,V_{\mathrm{ph}} and I_L=I_{\mathrm{ph}}. A connected neutral can carry the vector sum of unbalanced branch currents.
Delta connection
In delta, the three branches form a closed loop, and each branch is connected across two lines. This gives V_L=V_{\mathrm{ph}}. For balanced branch currents, the line current magnitude is I_L=\sqrt3\,I_{\mathrm{ph}}. Under unbalanced conditions, calculate each line current as a phasor difference of its adjacent branch currents.
Worked example on a 400 V supply
Three identical 40 Ω resistors connected in star each receive approximately 231 V and draw about 5.77 A, which is also the line current. In delta, each resistor receives 400 V and draws 10 A. Each line then carries about 17.3 A. For the same supply and identical resistors, the delta load draws three times the line current and consumes three times the total real power.
How to choose a connection
Check the voltage rating of each winding or load branch, the supply voltage, and whether the load needs a neutral. Star and delta can both serve balanced three-phase loads. Required branch voltage and equipment design determine the choice.

cOUEIchZGZFVKfMrrzR
I’m amazed, I mst say. Seldo do I encounhter a bkog that’s
eually educatife and interesting, and without a doubt, you
have hit thee nail oon the head. The problem is an issje tat not enough mmen andd women are
spoeaking intelligently about. Now i’m very happy thbat I
caje across this in my hunt for something concerning this.
xnxx